EasyManua.ls Logo

ABB RELION REX640 - Page 1861

ABB RELION REX640
1960 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Figure 984: Drop-off period is shorter than the set Reset delay time
When the drop-off period is shorter than the set
Reset delay time
, as described
in
Figure 984
, the input signal for the definite timer (here: timer input) is active,
provided that the current is above the set
Start value
. The input signal is inactive
when the current is below the set
Start value
and the set hysteresis region. The
timer input rises when a fault current is detected. The definite timer activates
the START output and the operate timer starts elapsing. The Reset (drop-off)
timer starts when the timer input falls, that is, the fault disappears. Another fault
situation occurs before the reset (drop-off) timer has elapsed. This causes the
activation of the OPERATE output, since the operate timer already has elapsed.
1MRS759142 F
General function block features
REX640
Technical Manual
1861

Table of Contents

Other manuals for ABB RELION REX640

Related product manuals