7360 ISAM FX-16 shelf cabling
110
ANSI Hardware Installation Manual
3HH-12893-AAAA-TCZZA Issue: 09
DRAFT
5 Tighten the nuts back on the power terminals with a torque of 65 lbf-in. maximum.
6 Place the safety cover back in its location and fasten the screws.
7 Turn on the A and B power from the power distribution frame to the rack.
8 Verify that the BAT A and BAT B LEDs are green.
9 Switch the A and B circuit breakers to the ON position.
10 Verify that the fans spin.
11 STOP. This procedure is complete.
Procedure 18 To disconnect the power cables
Use the following procedure when the power cables need to be disconnected on 7360 ISAM FX-
16.
1 Before disconnecting the power cables, ensure that power to the cables has been
disconnected.
2 Switch off the circuit breakers for BAT A and BAT B
3 Disconnect the battery cables BAT A and BAT B
4 Disconnect the BATRET cables RET A and RET B
5 STOP. This procedure is complete.
Warning — If the following sequence is not followed exactly, there can
be a possible fire hazard.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Nokia 7360 Intelligent Services Access Manager FX Series and is the answer not in the manual?

Nokia 7360 Intelligent Services Access Manager FX Series Specifications

General IconGeneral
BrandNokia
Model7360 Intelligent Services Access Manager FX Series
CategoryNetwork Hardware
LanguageEnglish

Related product manuals