Installing racks
68
ANSI Hardware Installation Manual
3HH-12893-AAAA-TCZZA Issue: 09
DRAFT
Figure 15 Securing the rack to the floor (non-seismic qualified installation)
3 Position the rack over the hole pattern.
4 Install the threaded rod and other hardware; see Figure 15.
5 Use the level to check leveling and alignment of the rack at the base, top, and both sides.
Tighten the hex nuts.
1/2 in.-13 Hex nut
1/2 in.-13 Concrete floor anchor
Anchor setting tool
not included in the kit
shown for reference only
1/2 in. Split lockwasher
1/2 in.-13 x 3 1/2 in. Threaded rod
1/2" in. Steel flat washer
Anchor plate
(part of the rack ssembly)
Adapter plate
(part of the rack ssembly)
7360 ISAM FX 7 ft rack assembly
shown for reference only
22366
Note — The maximum shim height to achieve the allowable vertical
deviation is 0.75 in. (19 mm).