7360 ISAM FX-12 shelf cabling
176
ANSI Hardware Installation Manual
3HH-12893-AAAA-TCZZA Issue: 09
DRAFT
10.5.3 Power cables
This section provides information about the types of power connection cables, cable
routing, and a procedure for connecting the power cables on the 7360 ISAM FX-12.
10.5.3.1 Power cable type
The 7360 ISAM FX-12 requires the use of an 2 AWG power cable.
10.5.3.2 Power cable routing and connection
The power cables are routed through the left side of the rack and can then be routed
to the power distribution terminal block located on the bottom of the shelf; see
Figure 81.
Note 1 — The color of the power cables must be according to
local installation practices.
Note 2 — Nokia recommends the following crimp lugs and
crimp lug tool:
• input power lug: 2 AWG, 90C, Burndy YA2CL-2NT14 or
equivalent.
• 2 AWG 1/4 in. stud with 5/8 in. spacing, dual-hole copper
lug, long barrel, peep, uses Burndy Die Code 10. See
Burndy catalog for additional tool options.
Note 3 — All required washers and nuts are included with the
shelf.