ANSI Hardware Installation Manual Installing a 7360 ISAM FX-8 shelf
Issue: 09 3HH-12893-AAAA-TCZZA 223
DRAFT
13 Installing a 7360 ISAM FX-8 shelf
13.1 Overview
13.2 Mounting the 7360 ISAM FX-8 shelf in a 19 in. rack
13.3 Mounting the 7360 ISAM FX-8 shelf in a 23 in. rack
13.4 Installing or replacing a fan unit in a 7360 ISAM FX-8 shelf
13.1 Overview
This chapter provides the steps to install a 7360 ISAM FX-8 shelf in a standard CO
equipment rack, including procedures for:
• Mounting the 7360 ISAM FX-8 shelf in a 19 in. rack
• Mounting the 7360 ISAM FX-8 shelf in a 23 in. rack
• Installing or replacing a fan unit in a 7360 ISAM FX-8 shelf
The 7360 ISAM FX-8 is suitable for the following:
• rack mounting on concrete floors or other non-combustible surfaces with the use
of a drip tray
• use in an installation using an IBN or a CBN
• use in:
• network telecommunication facilities
• locations where the NEC applies
• OSP
Warning — The 7360 ISAM FX-8 is intended to be installed in
a restricted access location (RAL) in accordance with the
applicable requirements of NEC or CEC. The local authorities
have jurisdiction. This unit is intended to be installed by
qualified service personnel only. Observe the following for the
7360 ISAM FX-8.
• Connect to a reliably grounded −48 V dc SELV source that
is grounded in the same building.
• Provide branch circuit overcurrent protection that is rated as
50 A with 8 AWG copper conductors.
• Incorporate a readily accessible disconnect device that is
suitably approved and rated in the field wiring.