Installing a 7360 ISAM FX-12 shelf
154
ANSI Hardware Installation Manual
3HH-12893-AAAA-TCZZA Issue: 09
DRAFT
9.2 Mounting the 7360 ISAM FX-12 shelf
The 7360 ISAM FX-12 shelf can be mounted:
• vertically in a seismic 19 in. rack (17.5 in. opening)
9.2.1 7360 ISAM FX-12 rack mounting configurations
Table 7 describes the vertical rack configurations for a 7360 ISAM FX-12 shelf in a
seismic 19 in. rack. Each shelf occupies 15.5 RU.
Table 7 Vertical mounting configurations for 7360 ISAM FX-12 in a seis-
mic 19 in. rack
9.2.2 Parts list
The following parts are required:
• 7360 ISAM FX-12 shelf (NFXS-G)
• grounded seismic19 in. rack that can accommodate the 7360 ISAM FX-12 shelf
• heat and fiber baffle kit
• fan unit, if replacing (BFAN-I)
• 2 AWG power lug
• general facilities card, if replacing (NGFC-I)
• cables:
• 50-pin micro DSUB connector
• DB-9 connector
• RJ-45 connector
• 6-pin wire-wrap right angle header connector
• 120-pin FCI power blade connector
• 12 mm pan head screws (10 per shelf unit)
Rack unit EIA standard 19 in. rack (17.75 in.)
SR 1 NFXS-G
7360 ISAM FX-12 heat and fiber baffle kit
Fan 1 BFAN-I (with fan filter)
SR 2 NFXS-G
7360 ISAM FX-12 heat and fiber baffle kit
Fan 2 BFAN-I (with fan filter)