EasyManua.ls Logo

Omron FQ2-S/CH Series

Omron FQ2-S/CH Series
590 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Basic Troubleshooting
436
FQ2-S/CH User’s Manual
Restoring a Sensor Connection
If you cannot connect to a sensor because the sensor is not detected in the [Sensor List] and the IP address
set in the sensor is unknown, you can execute [Re-assign IP forcibly] to forcibly change the IP address of the
sensor and connect.
The sensor’ IP address will be re-assigned as shown below based on the IP address settings of the Touch
Finder (PC Tool) that is connected to the sensor.
Execute this function with the Touch Finder (PC Tool) in a one-to-one connection with the sensor. If connected to
multiple sensors, IP address assignment will be performed for all sensors and reconnection will not take place nor-
mally.
The reassign IP address function is valid for Version 1.84 and later sensors.
1 Configure the network settings (IP address, subnet mask, and Default gateway) of the Touch
Finder (PC Tool).
2 Connect the sensor and the Touch Finder (PC Tool) in a one-to-one connection.
(If the sensor is connected via a network, disconnect the sensor from the network.)
3 Press (Run Mode) - [TF settings] - [Re-as-
sign IP forcibly].
4 Make sure that the sensor and Touch Finder are
connected in a one-to-one connection, and
press [Yes].
Example: Settings on computer
[IP]
[Subnetmask]
[Defaultgateway]
: 10.5.5.50
: 255.255.255.0
: 10.5.5.1
Settings on FQ2
[IP]
[Subnetmask]
[Defaultgateway]
: 10.5.5.XXX
: 255.255.255.0
: 10.5.5.1
XXX: The host part is automatically assigned
Important

Table of Contents

Related product manuals