1276 HEIDENHAIN Technical Manual MANUALplus 620
Module 9276 Write operand contents into the log
The module writes the contents of PLC operands into the error log file. The
entry can be given a special identifier for fast finding or later editing.
A buffer of approx. 210 bytes is available for the data to be written (including
the entry identification).
The operands M/I/O/C/T are stored in binary format (e.g.110101), the operands
B/W/D in hexadecimal format.
Call:
PS B/W/D/K <Identifier for operand name>
0: M (marker)
1: I (input)
2: O (output)
3: C (counter)
4: T (timer)
5: B (byte)
6: W (word)
7: D (double word)
PS B/W/D/K <Address of the first operand>
PS B/W/D/K <Number of operands>
PS B/W/D/K/S<Log identifier>
–1: No entry
PS B/W/D/K <Priority>
0: Information
1: Warning
2: Error
CM 9276
Error recognition:
Marker Value Meaning
NN_GenApiModule
Error
0 Entry was written
1 Error code in NN_GenApiModuleErrorCode
NN_GenApiModule
ErrorCode
1 Invalid priority
2 Invalid identifier for operand name
3 Invalid first operand address
4 Sum of first operand address and number of
operands invalid
5 Address is not a word/double-word address
12 No string end identifier
20 Module was not called in a spawn or submit
job
36 Entry in the log was truncated after 210
characters