1048 HEIDENHAIN Technical Manual MANUALplus 620
6.19.3 PWM frequencies with the CC 61xx
In MP_ampPwmFreq, you assign different PWM frequencies to the CC 61xx
controller groups.
There are three fundamental PWM frequencies: 3.333 kHz, 4 kHz and 5 kHz.
A control loop is operated at the fundamental PWM frequency or at double the
fundamental PWM frequency (6.666 kHz, 8 kHz, 10 kHz).
The same PWM frequency must be assigned to both PWM outputs of a
controller group with MP_ampPwmFreq. Otherwise, the DSP error message
C440 PWM frequency <axis> incorrect will appear.
Controller group 1: X51, X52
Controller group 2: X53, X54
Controller group 3: X55, X56
In MP_ampPwmFreq, enter the PWM frequency.
MP_ampPwmFreq
PWM frequency
Available from NCK software version: 597 110-01.
Format: Selection menu
Selection: 0
5 kHz (for HEIDENHAIN inverters)
3.333 kHz
4.166 kHz
5 kHz
6.666 kHz
8.333 kHz
10 kHz
Default: 0
Access: LEVEL3
Reaction: RESET
Settings in the configuration editor MP number
Axes
ParameterSets
[Key name of the parameter set]
CfgPowerStage
ampPwmFreq
CfgCurrentControl
iCtrlPwmType
401204
401003