936 HEIDENHAIN Technical Manual MANUALplus 620
6.16.24 Motor with wye/delta switchover
The parameter object CfgServoMotor is not required for:
Virtual axes (MP_axisMode = Virtual)
Axes that are for display only (MP_axisMode = Display)
Analog axes (MP_axisMode =Analog)
Define different parameter sets if a wye/delta connection switchover is carried
out for an asynchronous motor. Use the Modules 9434 and 9435 to activate
the parameter set for operation with wye connection or operation with delta
connection (see "Switching Parameter Sets" on page 398).
For the two operating modes, you can use different machine parameters for
the current and speed controllers:
The switchover can be carried out during standstill or with a revolving spindle.
With Module 9173, a monitoring function dependent on the speed can be
realized for the wye/delta switchover of the spindle. You can interrogate the
current spindle status with reference to the wye/delta switchover with
Module 9174.
Performing a wye/delta connection switchover:
Switch the drive controller off by using PP_AxDriveOnRequest.
Use Module 9434 to select the corresponding parameter set.
Use Module 9435 to check if this parameter set is active.
Switch the drive controller back on by using PP_AxDriveOnRequest.
MP_starDelta
Motor with wye/delta switchover
Available from NCK software version: 597 110-01.
Format: Selection menu
Selection: star-connection
Wye connection
delta-connection
Delta connection
Default: star-connection
Access: LEVEL3
Reaction: RESET
Settings in the configuration editor MP number
Axes
ParameterSets
[Key name of the parameter set]
CfgServoMotor
starDelta 401302
The contactor for the wye/delta switchover must not be switched under
load!