1562 HEIDENHAIN Technical Manual MANUALplus 620
MP_condition
Condition for sending the strobe to the PLC
Available from NCK software version: 597 110-02.
Format: Selection menu
Selection: COND_ALWAYS
Strobe is output with every programmed S code
COND_ST
Strobe is output only if spindle speed changes
COND_GP
Strobe is output only if gear range changes
If the parameter is missing from the configuration, the strobe is 
always output.
Default: COND_ST
Access: LEVEL3
Reaction: RESET
MP_signal
Symbolic name or number of the PLC marker that is set when 
the function is decoded.
Format: String 
Input: Max. 80 characters
If you have not entered a value in the parameter 
MP_acknowledge, resetting this marker means an 
acknowledgment of the strobe.
No entry: The data connected with the output of the strobe is 
saved without synchronization with the PLC program and the 
output is immediately acknowledged.
Default: No entry, value optional
Access: LEVEL3
Reaction: RESET
MP_acknowledge
Symbolic name or number of the PLC marker that is set for 
acknowledging the strobe.
Available from NCK software version: 597 110-02.
Format: String 
Input: Max. 80 characters
No entry: The strobe is reset with the PLC marker entered in 
MP_signal.
Default: No entry, value optional
Access: LEVEL3
Reaction: RESET