1732 HEIDENHAIN Technical Manual MANUALplus 620
Module 9073 Copy a string into a byte block
The control copies a PLC string into the word range of the PLC. The control
does not check whether the string consists of valid ASCII characters. The
programmed length of the string is always copied, regardless of any end-of-
string identifiers (0x00). If there are any ASCII special characters or an end-of-
string identifier (0x00) in the copied string, the contents of the string will not
be displayed correctly in the PLC diagnostics.
Call:
PS K/B/W/D <Target address of byte block>
PS K/B/W/D <Length of byte block>
PS K/B/W/D <PLC string>
CM 9073
Error recognition:
Marker Value Meaning
NN_GenApiModule
Error (M4203)
0 PLC string copied into byte block
1 Error. See NN_GenApiModuleErrorCode
(W1022)
NN_GenApiModule
ErrorCode (W1022)
1 Invalid target address of the programmed
byte block
2 Invalid length of the programmed byte block
(up to 127 characters permitted)
4 Invalid sum of the target address and the
programmed block length
11 Invalid source string