236 HEIDENHAIN Technical Manual MANUALplus 620
Power consumption of a PLA-H 08-04-04 I/O module:
Without load: 2.6 W
Under full load: 4.5 W
X46 to X49: Analog
inputs
Pin layout
X66 to X67: Analog
output
Pin layout
X81 to X82:
Connection for Pt
100
Pin layout:
HEIDENHAIN recommends:
Preferably use a conductor cross section of 0.34 mm
2
if you use stranded
wires with wire-end sleeves. This cross section can be clamped
appropriately and ensures a reliable terminal connection.
If you use stranded wires with wire-end sleeves and a conductor cross
section of 0.5 mm
2
, the Weidmüller PZ 6/5 crimping pliers (setting 0.25–
0.5 mm
2
) must be used for crimping. In this case, orient the crimped wire-
end sleeve before inserting it into the socket connector. If crimping pliers
from other manufacturers are used for crimping conductors with a cross
section of 0.5 mm
2
, the crimped wire-end sleeves cannot be inserted into
the socket connector and clamped appropriately, and therefore do not
result in a reliable terminal connection.
Connecting termi-
nals
Assignment
1a/1b –10 V to +10 V (input)
2a/2b 0 V (reference potential)
3a/3b Shield
Connecting termi-
nals
Assignment
1a/1b –10 V to +10 V (output)
2a/2b 0 V (reference potential)
3a/3b Shield
Connecting termi-
nals
Assignment
1a/1b I+ Constant current for Pt 100
2a/2b U+ Measuring input for Pt 100
3a/3b U– Measuring input for Pt 100
4a/4b I– Constant current for Pt 100
5a/5b Shield