January 2012 3.26 MB 620T Machine Operating Panel 273
X31: MB 620T, 
permissive button / 
NC start / NC stop
Standard wiring of connection X31 for MB 620T without FS:
Pin layout of MB 620T FS:
NC Start and NC Stop are normally-open contacts on the MB 620 (FS).
Connecting 
terminals
Assignment
1 Reserved (do not use)
2 Reserved (do not use)
3 Reserved (do not use)
4 Reserved (do not use)
5 NC Start
a
a. With standard wiring
6 Reserved (do not use)
7 NC Start power supply (+24 V NC)
a
8NCStopa
9 Reserved (do not use)
10 NC Stop power supply (+24 V NC)
a
Connecting 
terminals
Assignment
1 Optional: Permissive key channel A / terminal 1 (+24 V)
2 Optional: Permissive key channel A / terminal 2
3 Optional: Permissive key channel B / terminal 1 (+24 V)
4 Optional: Permissive key channel B / terminal 2
5 NC Start channel A / terminal 1 a
6 NC Start channel B / terminal 2 a
7 NC Start shared terminal (+24 V NC)a
8 NC Stop channel A / terminal 1a
9 NC Stop channel B / terminal 2a
10 NC Stop shared terminal (+24 V NC)
a
a. With standard wiring
Please note that the MB 620T is powered by +24 V NC.
For the entire HSCI system, the +24 V NC supply voltage is required to be 
safely separated voltage. The +24 V NC supply voltage must not, under any 
circumstances, be connected with the +24 V PLC supply voltage, because 
this removes the double basic insulation.