January 2012 6.16 The Control Loop 887
Expanded current 
controller 
bandwidth
(only CC 61xx)
For axes with rigidly connected mechanics it may make sense to adjust the 
current control loop using the maximum possible bandwidth to attain high 
gains in the superimposed velocity control loop. For the CC 61xx controller 
unit there are two procedures for increasing the bandwidth of the current 
control loop:
 Using machine parameter MP_iCtrlAddInfo to increase the controller 
factors in the current control loop,
 Proportionally differentiating feedforward (D feedforward) to optimize the 
command action of the current control loop (MP_iCtrlDiffFreqFF 
parameter).
Increased controller factors in the current control loop:
The dead time in the current control loop is the decisive factor for the 
attainable controller factors, and therefore for the attainable bandwidth. With 
parameter MP_iCtrlAddInfo, you can activate compensation of this dead 
time. After activation, you have to repeat the current controller adjustment. 
Usually you can then set considerably higher current controller factors. The 
higher the controller factors, the larger the bandwidth of the current controller. 
The bandwidth of the current control loop can be evaluated with the Bode 
diagram function of the TNCopt commissioning and diagnostic software (see 
TNCopt User's Manual).
However, the noise in the current—and as a result, the loudness of the drive—
increase when the current controller bandwidth is increased.
D feedforward for optimization of the current controller command 
action:
With parameter MP_iCtrlDiffFreqFF, you activate feedforward with 
proportionally differentiating behavior for the torque-generating current. This 
way you achieve an optimized command action of the current controller. 
The parameter MP_iCtrlDiffFreqFF indicates the cutoff frequency in Hertz 
[Hz] up to which feedforward is active. When this cutoff frequency is reached, 
feedforward is deactivated by a low-pass element. It is therefore also referred 
to as PDT
1
 feedforward in the following. 
The following table shows the maximum possible cutoff frequency depending 
on the PWM frequency of the drive. The higher the cutoff frequency, the larger 
the bandwidth of the current controller regarding its command action. At the 
same time, however, the noise in the current—and as a result, the loudness 
of the drive—increase. If you enter 0 Hz, feedforward is deactivated.
Settings in the configuration editor MP number
Axes
ParameterSets
[Key name of the parameter set]
CfgCurrentControl
iCtrlDiffFreqFF
iCtrlAddInfo
401007
401008