972 HEIDENHAIN Technical Manual MANUALplus 620
Module 9367 I
2
t monitoring
The module reports
 an I
2
t early warning
 an I
2
t error (temperature exceeded)
The I
2
t monitoring reported by the module is given with respect to the first I
2
t 
monitor response (power module or motor), if both I
2
t monitors are activated 
(MP_motFactorI2t, MP_ampFactorI2t). 
The I
2
t early warning is withdrawn as soon as the limit for reset is reached. For 
the response behavior, see "Limit values" on page 969.
Constraints:
 Unconnected axes respond with all error bits as 0. 
 The I
2
t monitor responds if the current value exceeds 110 % of the rated 
current.
 The "I
2
t early warning" is set approx. 200 ms before the limit takes effect. 
The "I
2
t monitoring" is set when the limit is reached. 
 For the spindle axis, only the I
2
t early warning is possible. 
Call:
CM 9367
PL D <>I2t early warning, bit-encoded>
(Bit 0 represents logic axis 0, etc.)
PL D <>I2t error, bit-encoded>
(Bit 0 represents logic axis 0, etc.)
Error recognition: 
Marker Value Meaning
NN_GenApiModule
Error
0 No error
1 Control has no current controller