982 HEIDENHAIN Technical Manual MANUALplus 620
MP_powStatusCheckOff
Suppress error messages of the HEIDENHAIN supply units
Available from NCK software version: 597 110-01.
Format: Numerical value 
Input: Bit 0 – Status signals that are already active during control 
power-up.
0: Missing signals are ignored
1: Missing signals are evaluated
Bit 1 – ERR.UZ.GR
 signal
0: Error message is not suppressed
1: Error message is suppressed
Bit 2 – ERR.TMP
 signal
0: Error message is not suppressed
1: Error message is suppressed
Bit 3 – Reserved
Bit 4 – ERR.IZ.GR
 signal
0: Error message is not suppressed
1: Error message is suppressed
Bit 5 – RDY.PS signal
0: Error message is not suppressed
1: Error message is suppressed
Bit 6 – ERR.ILEAK
 signal
0: Error message is not suppressed
1: Error message is suppressed
Bit 7 – PF.PS.AC
 signal
(only on CC 61xx / UEC 11x)
0: Error message is not suppressed
1: Error message is suppressed
Bit 8 – PF.PS.DC signal
(only on CC 61xx / UEC 11x)
0: Error message is not suppressed
1: Error message is suppressed
Bit 9 – Monitoring of DC-link voltage Uz or 
LIFTOFF function
(only on CC 61xx / UEC 11x)
0: Uz monitoring and LIFTOFF function are active
1: Uz monitoring and LIFTOFF function are not active
Default: 0
Access: LEVEL3
Reaction: RESET