Read “General Safety Guidelines and Warnings” on page 161, with particular attention
to “Chassis Lifting Guidelines for a QFX3008-I Interconnect Device” on page 175.
Ensure that the device has been safely powered off (see “Powering Off a QFX3008-I
Interconnect Device” on page 296) and that you have unplugged (disconnected) the
power cords. Remove three-phase wiring trays from the chassis and move them
separately, leaving the power cords attached to the wiring trays (see “Removing a
Wiring Tray from a QFX3008-I Interconnect Device” on page 326).
Ensure that you have disconnected any cables or wires attached to the device.
Ensure that you have the following parts and tools available to remove the switch:
A Phillips (+) screwdriver, number 2. You might also need a number 3 Phillips (+)
screwdriver, depending on the size of your rack mounting screws.
A mechanical lift rated for at least 750 lb (340.2 kg). If you do not have a lift rated for
750 lb (341 kg), you must remove all components from the chassis and use a lift rated
for at least 250 lb (114 kg). The weight of an empty QFX3008-I Interconnect device
and midplane is approximately 205 lb (93 kg).
WARNING: Becauseof the QFX3008-I Interconnect devicesize and weight,
werequire the use of a mechanical lift to install the QFX3008-I Interconnect
device in a rack or cabinet or to move the device from one location to
another.
CAUTION: The handleson the QFX3008-I Interconnectdevice are designed
to help maneuver the chassis from the mechanical lift to the mounting
shelves in the rack. Do not attempt to lift the chassis using the handles.
To remove a QFX3008-I Interconnect device from a rack or cabinet:
1. Use the appropriate Phillips (+) screwdriver to remove the mounting screws that
attach the chassis front-mounting brackets to the rack or cabinet.
2. Place the removed screws in a labeled bag. You will need them when you reinstall
the chassis.
3. Move the lift to the rack and position it so that its platform is centered about 0.5 in.
(1.27 cm) below the bottom of the device chassis and as close to it as possible.
4. Carefully slide the device from the mounting shelves attached to the rack onto the
lift.
5. Use the number 2 Phillips (+) screwdriver to remove the mounting hardware from the
rack.
6. Use the lift to transport the device to its new location.
Related
Documentation
Installing and Connecting a QFX3008-I Interconnect Device on page 223
301Copyright © 2012, Juniper Networks, Inc.