AC Power Supply in a QFX3008-I Interconnect Device on page 52
AC Power Supply LEDs on a QFX3008-I Interconnect Device on page 394
AC Power Cord Specifications for a QFX3008-I Interconnect Device with Three-Phase
Wye Wiring Trays on page 142
Power Requirements for a QFX3008-I Interconnect Device
Table 48 on page 139 lists the power requirements for different hardware components
of a QFX3008-I Interconnect device under typical voltage conditions.
Table 48: QFX3008-I Interconnect Device Component Power Requirements
Equivalent Input PowerComponents
3100 W (at normal fan speed, typical input power)
4500 W (at maximum fan speed, maximum input power)
Chassis, including Control Boards, rear cards, cooling system,
and power components
190 W (typical input power)
240 W (maximum input power)
16-port QSFP+ front card (including optical transceivers)
Related
Documentation
Calculating Power Requirements for a QFX3008-I Interconnect Device on page 143
AC Power Specifications for a QFX3008-I Interconnect Device with Three-Phase Delta
Wiring Trays on page 138
AC Power Specifications for a QFX3008-I Interconnect Device with Three-Phase Wye
Wiring Trays on page 138
AC Power Cord Specifications for a QFX3008-I Interconnect Device with Single-Phase
Wiring Trays
Most sites distribute power through a main conduit that leads to frame-mounted power
distribution panels, one of which can be located at the top of the rack that houses the
device. Three AC power cords connect each wiring tray to the power distribution panel.
Six detachable AC power cords, each 2.5 m (approximately 8 ft) long, are supplied with
the device. The appliance coupler at the female end of the cord inserts into one of the
three appliance inlets on the faceplate of the single-phase wiring tray. The coupler is
type C19 as described by International Electrotechnical Commission (IEC) standard
60320. The plug at the male end of the power cord fits into the power source receptacle
that is standard for your geographical location.
WARNING: TheQFX3008-IInterconnectdevice is pluggabletype A equipment
installed in a restricted-access location. It has a separate protective earthing
terminalprovided on the chassisin addition to the grounding pin of the power
supply cord. This separate protective earthing terminal must be permanently
connected to earth.
139Copyright © 2012, Juniper Networks, Inc.
Chapter 10: Planning QFX3008-I Power Requirements

Table of Contents

Other manuals for Juniper QFX Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Juniper QFX Series and is the answer not in the manual?

Juniper QFX Series Specifications

General IconGeneral
CategorySwitch
SeriesQFX
Form Factor1U, 2U, and modular chassis options
Power SupplyRedundant, hot-swappable power supplies
Coolinghot-swappable fans
Virtual ChassisSupported on certain models
Typical UseData center, cloud
Operating SystemJunos OS
ManagementCLI
Key FeaturesHigh performance, low latency, automation
LatencySub-microsecond latency
Port DensityVaries by model (e.g., QFX5100: up to 48x10GbE + 6x40GbE)