January 2012 6.22 Diagnosis with the Online Monitor (OLM) 1183
Status of the axes
(Diag State)
To select the Diag State function:
Press the Login Ipo (or Login SimIpo) soft key.
Press the Axes soft key.
Press the Diag State soft key.
The function displays the status of the following binary variables (the
descriptions refer to the status "true"):
Variable Display
OwnFeedhold No feed-rate enable from the PLC for this axis
OtherFeedhold No feed-rate enable from the PLC for an axis of the
kinematics
NewSlope Internal use
NoAntriebFrei No drive enable by the PLC
OwnPosCtrl Position feedback control not active
OtherPosCtrl Position feedback control not active in an axis of the
kinematics
Override=0 Override at 0%
OffsetCtrl Internal use
TakeCycData Internal use
PlcMaxFeed=0 MaxFeed from the PLC is 0
TsMaxFeed=0 MaxFeed from the touch-probe table and/or from
parameter "maxTouchFeed" is 0
WorkingOutLag Following error is corrected