1316 HEIDENHAIN Technical Manual MANUALplus 620
During start-up, the control detects that the required machine parameter files
are not available on the PLC partition. The start-up process is interrupted. The
following dialog box appears:
(The machine parameters for configuring the conversational language are also
stored on the PLC partition. Since these parameters are not available at
present, English is set as the default language.)
Use TNCremoNT to establish a connection to the control (the last valid
Ethernet configuration is effective)
Copy the data you saved before, with TNCbackup for example, back to the
PLC partition
Shut down the control by pressing the OFF soft key.
Restart the control.
The system should work properly again.
Control start-up
with faulty
configuration
If configuration errors occur during control start-up, the Error during start-
up message appears instead of Power interrupted.
Also, the error messages for the incorrect configuration data, which are
triggered by the applications, are displayed individually.