January 2012 7.4 Switching the Control On/Off 1323
The entry in MP_powerOffPort has the following meaning:
 The corresponding PLC output is set if the requirements described above 
are fulfilled (shutdown with POWEROFF setting or shutdown with Module 
9279 – mode 2).
 No entry: No PLC output is set.
MP_powerOffPort
PLC output to be set after shutdown
Available from NCK software version: 597 110-01.
Format: Numerical value 
Input: 0 to 31: Corresponds to PLC outputs I0 to I31 for systems 
without HSCI
For systems with HSCI, please see the device-specific table.
No entry: Do not set PLC output.
Default: No value, parameter optional
Access: LEVEL3
Reaction: NOTHING
After shutdown, the control waits for the time defined in MP_powerOffDelay 
before setting the PLC output.
MP_powerOffDelay
Delay time until PLC output is set
Available from NCK software version: 597 110-01.
Format: Numerical value 
Input: 0 to 1000 [s]
Default: No value, parameter optional
Access: LEVEL3
Reaction: NOTHING
Module 9189 Shut down the control
Module 9189 shuts down the control. The PLC is not executable after 
shutdown. The message windows, which appear during shutdown via soft 
key, do not appear.
Call:
CM 9189
Error recognition: 
Marker Value Meaning
NN_GenApiModule
Error
0 Control was shut down
1 Error code in NN_GenApiModuleErrorCode
NN_GenApiModule
ErrorCode
20 Module was not called in a spawn job or 
submit job