1322 HEIDENHAIN Technical Manual MANUALplus 620
After shutdown has been initiated, the control waits for the time defined in
MP_maxTermTime before starting the shutdown.
MP_maxTermTime
Delay time until control is shut down
Available from NCK software version: 597 110-01.
Format: Numerical value
Input: 0 to 1000 [s]
Default: 0
Access: LEVEL3
Reaction: NOTHING
Both optional parameters MP_powerOffDevice and MP_powerOffSlot are
relevant only for HSCI systems (e.g. TNC 620). No values are to be entered for
controls without HSCI.
For an HSCI system, enter the bus address of the HSCI PL in the parameter
MP_powerOffDevice, e.g. the bus address of a PL 62xx or UEC 11x at which
the control is to set a PLC output after shutting down.
MP_powerOffDevice
Bus address of the HSCI device
Available from NCK software version: 597 110-04.
Format: Numerical value
Input: 0 to 20
Default: No value, parameter optional
Access: LEVEL1
Reaction: NOTHING
For an HSCI system, enter in parameter MP_powerOffSlot the number of a
slot of the HSCI device defined under MP_powerOffDevice at which a PLC
output is to be set after shutdown. The system module of a PL 62xx or a
UEC 11x has the number 0.
MP_powerOffSlot
Number of the slot on the HSCI device (PL or UEC)
Available from NCK software version: 597 110-04.
Format: Numerical value
Input: 0 to 8
Default: No value, parameter optional
Access: LEVEL1
Reaction: NOTHING