1378 HEIDENHAIN Technical Manual MANUALplus 620
Module 9194 Alarm when operating time exceeded
The module activates a monitoring function in the NC, which sets a PLC
marker when the given maximum time for a PLC or NC operating hours
counter is exceeded. The marker is set the first time the maximum time is
exceeded, and then cyclically once per minute.
The marker can be delayed by max. 59 s the first time it is set. All values
greater than 2 147 483 648 (approx. 69 years) must be transferred as negative
numbers.
If you enter the value zero as the alarm threshold, the function is deactivated.
Call only in a submit job or spawn job.
Call:
PS B/W/D/K <Number of the operating time>
–3: Control on
–2: Machine on
–1: Program run
0 to 7: PLC operating times 1 to 8
PS B/W/D/K <Alarm threshold [s]>
PS B/W/D/K <Number of the alarm markers>
CM 9194
Error recognition:
Marker Value Meaning
NN_GenApiModule
Error
0 Alarm function activated
1 Incorrect transfer value, or module was not
called in a spawn or submit job