January 2012 6.16 The Control Loop 927
 Mode 1:
Enter MP_ampVoltProtection =  not installed – mode 1 if you want to 
operate synchronous motors without a weakened field. ((1) in the 
commissioning flow chart)
Field weakening for synchronous motors is deactivated, i.e. the field 
weakening current is always 0, regardless of the speed and load. Use this 
entry also for all asynchronous motors. MP2160 is without effect on them.
 Mode 2:
Enter MP_ampVoltProtection = installed – mode 2 if you want to 
operate the synchronous motor with a weakened field (check whether a 
voltage protection module must be used. ((2) in the commissioning flow 
chart).
This entry is intended for synchronous spindles and torque motors in turning 
mode. Here, field weakening is active in a wide speed range, i.e. the 
maximum speed nmax is much higher than the rated speed nrated (nmax 
>> nrated). The internal voltage Uemk at maximum speed in the motor leads 
to a considerable rise of the DC-link voltage if the power supply fails, so that 
the connected inverters and also the motor can get damaged. It is therefore 
necessary to install a voltage protection module (e.g. SM 110, see the 
"Inverter Systems and Motors" Technical Manual) as a protective measure.
The EcoDyn synchronous motors from HEIDENHAIN are operated with 
limited field weakening. No voltage protection module is necessary here.
 Select from the motor table the motors with the designation QSY1xxx EcoDyn 
or QSY1xxx EcoDyn EnDat for MP_motName
 Enter MP_ampVoltProtection = not installed – mode 3 if you use 
HEIDENHAIN EcoDyn synchronous motors. ((3) in the commissioning flow 
chart).
This entry is intended for axis motors in EcoDyn operation. Here, field 
weakening is only active in a relatively small speed range, i.e. the maximum 
speed nmax is not significantly higher than the rated speed nrated (nmax > 
nrated). The MANUALplus 620 calculates a voltage-dependent, maximum 
speed nmaxUz. This speed ensures that the internal voltage Uemk in the 
motor only leads to a limited rise of the DC-link voltage if the power supply 
fails. Using a voltage protection module is therefore not necessary. Please 
note that the voltage-dependent, maximum speed nmaxUz can be lower 
than the maximum speed in the motor table. Please take this into 
consideration during project planning.
U0 = entry U0 (no-load voltage) of the motor from the motor table
n
rated
 = entry N-N (rated speed) of the motor from the motor table
UZ = 800 V (maximum DC-link voltage if the power supply fails)
n
maxUz
800V
2
----------------
n
rated
⋅
U
0
--------------------------------------------=