928 HEIDENHAIN Technical Manual MANUALplus 620
Setting of MP_ampBusVoltage:
Regenerative module ((4) in commissioning flow chart)
The DC-link voltage for regenerative power modules are independent of the
line voltage UNetz. On regenerative HEIDENHAIN power modules it is 650 V
(MP_ampBusVoltage = 650) and on the regenerative Siemens modules 600
V or 625 V (MP_ampBusVoltage = 600 / 625).
Default setting of MP_ampVoltProtection has been made
Regenerative module
(e.g. UVR 150D)?
MP_ampBusVoltage = 650 (4)
YES
Stationary line voltage stable?
MP_ampBusVoltage = smallest
value of stationary DC-link voltage (6)
No
– Calculation of minimum line voltage (5)
– Series reactor taken into account
– Line voltage at machine installation site
taken into account
MP_ampBusVoltage =
actual
DC-link voltage
No
Line voltage stable under load?
MP_ampBusVoltage = smallest
value of dynamic DC-link voltage (7)
No
Setting MP_ampBusVoltage has been made
YES
YES