2. Multiply the maximum system power consumption by 3.41
= 6420 W x 3.41
System thermal output for a fully loaded switch configuration = 21,892 BTU/hr
NOTE: Using the maximum system power consumption values to calculate
the system thermal output often results in overprovisioning the cooling
systems. Typical power consumption is about one-third lower than these
calculated values.