The NCS 2002 requires a minimum of 3.5 inches (88.9 mm) of vertical rack space. To ensure that the
mounting is secure, use two to three NCS 2006 mounting screws on each side of the shelf. A shelf should
be mounted at the bottom of the rack if it is the only unit in the rack.
Note
In an ANSI rack, the chassis can be installed in the front or the middle position. In an ETSI rack, the
chassis is installed only in the front position.
Note
Procedure
Step 1
Verify that the proper fuse panel has been installed in the top mounting space. If a fuse panel is not present,
you must install one according to manufacturer instructions:
•
For a DC power supply, the fuse rating must not exceed 15A.
•
For an AC power supply, the fuse rating must not exceed 10A, 15A, or 20A. For North America, the
branch circuit protection must be rated 20A. The overcurrent/short circuit protection must be in accordance
with local and national electrical codes.
Step 2
Ensure that the shelf is mounted on the appropriate rack equipment:
•
23 inches (584.2 mm) or 19 inches (482.6 mm) for ANSI racks. The recommended 19-inch ANSI rack
for the NCS 2002 shelf is shown in the figure below
•
600 x 600-mm (23.6 x 23.6-inch) or 600 x 300-mm (23.6 x 11.8-inch) for ETSI racks.
Diagram 1 of the figure below shows the NCS 2002 shelf mounted on an ANSI rack in the middle position
using 19-inch mounting brackets
Cisco NCS 2000 Series Hardware Installation Guide
68
Mounting the Cisco NCS 2002 Shelf
DLP-L42 Mounting the NCS 2002 Shelf on a Rack (One Person)