To comply with EN50121-4:2006 - Railway applications, Electromagnetic compatibility, a shielded
cable must be used to connect to the EMS port. This cable must be less than 30 meters in length and
not placed in the 3 meter boundary, as defined in EN50121-4:2006, Table 2, note 1. Statement 8010
Warning
To comply with EN50121-4:2006 - Railway applications, Electromagnetic compatibility, DC power
cables must be less than 30 meter long. Statement 8011
Warning
Procedure
Complete the necessary task as applicable:
DLP-L72 Mounting NCS 2015 Shelf on a Rack (One Person), on page 319
DLP-L73 Mounting NCS 2015 Shelf on a Rack (Two People) , on page 322
DLP-L74 Mounting Multiple NCS 2015 Shelves on a Rack , on page 323
Stop. You have completed this procedure.
DLP-L72 Mounting NCS 2015 Shelf on a Rack (One Person)
This task allows one person to mount the shelf on a
rack.
Purpose
# 2 Phillips Dynamometric screwdriver
ETSI: 16 M6 x 20 mm pan-head Phillips
mounting screws
ANSI: 16 #12-24 x 0.50 inch pan-head Phillips
mounting screws
Tools/Equipment
nonePrerequisite Procedures
As neededRequired/As Needed
OnsiteOnsite/Remote
NoneSecurity Level
Cisco NCS 2000 Series Hardware Installation Guide
319
Mounting the Cisco NCS 2015 Shelf
DLP-L72 Mounting NCS 2015 Shelf on a Rack (One Person)