Procedure
Step 1
Complete DLP-L12 Opening the Standard Door of the NCS 2006 Shelf , on page 253.
Step 2
Complete the DLP-L13 Removing the Standard Door of the NCS 2006 Shelf , on page 255.
Stop. You have completed this procedure.
DLP-L12 Opening the Standard Door of the NCS 2006 Shelf
This task opens the standard door of the NCS 2006
shelf.
Purpose
#2 Phillips Dynamometric screwdriverTools/Equipment
•
NTP-L2 Mounting the Brackets in ANSI
Configuration , on page 163
•
Connect the chassis to the office ground. For
detailed instructions on how to ground the
chassis, see the Electrostatic Discharge and
Grounding Guide for Cisco NCS 2000 Series .
Prerequisite Procedures
RequiredRequired/As Needed
OnsiteOnsite/Remote
NoneSecurity Level
The NCS 2006 shelf has an ESD plug input and is shipped with an ESD wrist strap. The ESD plug input
is located on the outside of the shelf on the left side. It is labeled “ESD” on the top and bottom. Always
wear an ESD wrist strap and connect the strap to the ESD plug when working on the NCS. For detailed
instructions on how to wear the ESD wristband, see the Electrostatic Discharge and Grounding Guide for
Cisco NCS 2000 Series .
Note
Cisco NCS 2000 Series Hardware Installation Guide
253
Installing the Cisco NCS 2006 Door and Other Modules
DLP-L12 Opening the Standard Door of the NCS 2006 Shelf