Step 5
Align the screw holes on the left back air deflector with the screw holes on the left side of the chassis.
Step 6
Insert the screws and tighten them to a torque value of 11.5 in-lb (1.3 N-m).
Step 7
Place the 23-inch mounting bracket flush in the front position (see Diagram 1 of the figure below) or in the
middle position (see Diagram 3 of the figure below) against the right side of the chassis.
Step 8
Align the screw holes on the 23-inch mounting bracket with the screw holes on the right side of the chassis.
Step 9
Insert the screws and tighten them to a torque value of 11.5 in-lb (1.3 N-m).
Step 10
Place the 23-inch mounting bracket flush in the front position (see Diagram 1 of the figure below) or in the
middle position (see Diagram 3 of the figure below) against the left side of the chassis.
Step 11
Align the screw holes on the 23-inch mounting bracket with the screw holes on the left side of the chassis.
Step 12
Insert the screws and tighten them to a torque value of 11.5 in-lb (1.3 N-m).
Figure 109: Mounting the Brackets with Air Deflectors (Front-to-Back) on the NCS 2006 Shelf for ANSI Rack Configuration
Step 13
Return to your originating procedure (NTP).
NTP-L46 Mounting the Brackets in ETSI Configuration
This procedure helps in mounting the brackets on the
NCS 2006 shelf.
Purpose
Cisco NCS 2000 Series Hardware Installation Guide
174
Mounting the Brackets on NCS 2006 Shelf
NTP-L46 Mounting the Brackets in ETSI Configuration