Stop. You have completed this procedure.
NTP-L20 Replacing the Air Filter of the NCS 2006 Shelf Assembly
This procedure replaces the air filter of the NCS 2006
shelf assembly.
Purpose
New air filterTools/Equipment
•
NTP-L3 Mounting the NCS 2006 Shelf, on
page 189
•
Connect the chassis to the office ground. For
detailed instructions on how to ground the
chassis, refer to the Electrostatic Discharge and
Grounding Guide for Cisco NCS 2000 Series .
Prerequisite Procedures
As NeededRequired/As Needed
RemoteOnsite/Remote
Provisioning or higherSecurity Level
The air filters are single-use only. They must not be cleaned and reused. This is a Telcordia NEBS
requirement, GR-63-CORE Issue 4.
Note
Air filters must be inspected every quarter after the initial six month inspection. If they are dirty or clogged
with dust, they must be replaced with a new air filter.
Note
Cisco NCS 2000 Series Hardware Installation Guide
444
Maintaining the NCS 2002, NCS 2006, and NCS 2015 Shelves
NTP-L20 Replacing the Air Filter of the NCS 2006 Shelf Assembly