ANSI and ETSI:
#2 Phillips Dynamometric screwdriver
Medium slot-head screwdriver
Small slot-head screwdriver
Screws
Ground cable 13.3-mm² (#6 AWG) stranded
Listed pressure dual-holes lugs suitable for #8
AWG copper conductors
Wire cutters
Wire strippers
Crimp tool
Fuse panel
ANSI only:
Power cable (from fuse panel to assembly), #8
AWG, copper conductors, 194 degrees F [90
degrees C])
Wire wrapper
ETSI only:
Power cable (from fuse panel to power
modules), shipped with the NCS 2002 ETSI
Two-hole grounding lug, shipped with the NCS
2002 ETSI
Tools/Equipment
Connect the chassis to the office ground. For
detailed instructions on how to ground the
chassis, refer to the Electrostatic Discharge and
Grounding Guide for Cisco NCS 2000 Series .
Prerequisite Procedures
RequiredRequired/As Needed
OnsiteOnsite/Remote
NoneSecurity Level
Cisco NCS 2000 Series Hardware Installation Guide
77
Connecting Power and Ground
NTP-L35 Installing the Power and Ground to the NCS 2002 Shelf