EasyManua.ls Logo

Cisco NCS 2006 - DLP-L61 Measuring DC Voltage on the NCS 2006 Shelf; DLP-L61 Measuring DC Voltage on the NCS 2002 Shelf

Cisco NCS 2006
510 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
ANSI and ETSI:
•
#2 Phillips Dynamometric screwdriver
•
Medium slot-head screwdriver
•
Small slot-head screwdriver
•
Screws
•
Ground cable 13.3-mm² (#6 AWG) stranded
•
Listed pressure dual-holes lugs suitable for #8
AWG copper conductors
•
Wire cutters
•
Wire strippers
•
Crimp tool
•
Fuse panel
ANSI only:
•
Power cable (from fuse panel to assembly), #8
AWG, copper conductors, 194 degrees F [90
degrees C])
•
Wire wrapper
ETSI only:
•
Power cable (from fuse panel to power
modules), shipped with the NCS 2002 ETSI
•
Two-hole grounding lug, shipped with the NCS
2002 ETSI
Tools/Equipment
•
Connect the chassis to the office ground. For
detailed instructions on how to ground the
chassis, refer to the Electrostatic Discharge and
Grounding Guide for Cisco NCS 2000 Series .
Prerequisite Procedures
RequiredRequired/As Needed
OnsiteOnsite/Remote
NoneSecurity Level
Cisco NCS 2000 Series Hardware Installation Guide
77
Connecting Power and Ground
NTP-L35 Installing the Power and Ground to the NCS 2002 Shelf

Table of Contents