440 HEIDENHAIN Technical Manual MANUALplus 620
unit
103501
Unit of measure
Format: Selection menu
Input:
SECONDS:
Input in seconds [s]
PLC_CYCLES:
Input in number of PLC cycles
Default: SECONDS
RUN
LEVEL3
1528
value
103502
MP4110 / 4120
Default value for PLC timers/counters
Format: List [1 to 100]
Input: 0 to 1 000 000 [s or PLC cycles]
Default: 0 [s or PLC cycles]
RUN
LEVEL3
1528
CfgPlcFastInput
Configuration of fast PLC inputs;
Specifies the numbers, operands and edge detection. Keep in mind that the time between two edges
must be longer than the time from 'MP_CfgCycleTimes/ipoCycle'.
number
103701
MP4130
Numbers of fast PLC inputs
Format: List [0 to 4]
Input: 0 to 9999
Default: 0
RUN
LEVEL3
1532
significance
103702
MP4131
Activation criteria for fast PLC inputs
Format: List [0 to 4] with selection menu
Input:
lowActive:
Activate at LOW level
highActive:
Activate at HIGH level
allEdges:
Activate at both levels
disabled:
Switched off
RUN
LEVEL3
1533
operand
103703
(optional parameter)
PLC operand for fast PLC inputs
Name or number of the operand that is set
through the fast PLC input.
Format: List [0 to 4]
Input: String, max. 24 characters
RUN
LEVEL3
1533
Parameter
MP number
iTNC MP number
Function and input Behavior
Access
SW vers.
Page