EasyManua.ls Logo

Siemens SINAMICS G120 - p0628[0...n] Motor overtemperature rotor; Mot T_over rotor; r0630[0...n] Mot_temp_mod ambient temperature; Mod T_ambient; r0631[0...n] Mot_temp_mod stator iron temperature; Mod T_stator; r0632[0...n] Mot_temp_mod stator winding temperature; Mod T_winding

Siemens SINAMICS G120
924 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
2 Parameters
2.2 List of parameters
SINAMICS G120 Control Units CU240B-2/CU240E-2
102 List Manual (LH11), 01/2016, A5E33839529
Description: Defines the rated overtemperature of the squirrel cage rotor referred to ambient temperature in the motor
temperature model 2 (p0612.1 = 1).
Dependency: For 1LA7 motors (p0300), the parameter is pre-set as a function of p0307 and p0311.
Refer to: p0625
Notice: When selecting a standard induction motor listed in the catalog (p0300 > 100, p0301 > 10000), this parameter is
automatically pre-assigned and is write protected. Information in p0300 should be carefully observed when removing
write protection.
Note: When quick commissioning is exited with p3900 > 0, then the parameter is reset if a catalog motor has not been
selected (p0300).
Description: Displays the ambient temperature of the motor temperature model (models 2 and 3).
Description: Displays the stator iron temperature of the motor temperature model (models 2 and 3).
Note: For motor temperature model 1 (p0612.0 = 1), this parameter is not valid:
Description: Displays the stator winding temperature of the motor temperature model.
Dependency: Refer to: F07011, A07012, A07910
Description: Displays the rotor temperature of the motor temperature model (models 2 and 3).
Note: For motor temperature model 1 (p0612.0 = 1), this parameter is not valid:
p0628[0...n] Motor overtemperature rotor / Mot T_over rotor
Access level: 4 Calculated: p0340 = 1,2 Data type: FloatingPoint32
Can be changed: C(3), U, T Scaling: - Dyn. index: MDS
Unit group: 21_2 Unit selection: p0505 Func. diagram: 8018
Min Max Factory setting
20 [K] 200 [K] 100 [K]
r0630[0...n] Mot_temp_mod ambient temperature / Mod T_ambient
Access level: 4 Calculated: - Data type: FloatingPoint32
Can be changed: - Scaling: p2006 Dyn. index: MDS
Unit group: 21_1 Unit selection: p0505 Func. diagram: 8018
Min Max Factory setting
- [°C] - [°C] - [°C]
r0631[0...n] Mot_temp_mod stator iron temperature / Mod T_stator
Access level: 4 Calculated: - Data type: FloatingPoint32
Can be changed: - Scaling: p2006 Dyn. index: MDS
Unit group: 21_1 Unit selection: p0505 Func. diagram: 8018
Min Max Factory setting
- [°C] - [°C] - [°C]
r0632[0...n] Mot_temp_mod stator winding temperature / Mod T_winding
Access level: 2 Calculated: - Data type: FloatingPoint32
Can be changed: - Scaling: p2006 Dyn. index: MDS
Unit group: 21_1 Unit selection: p0505 Func. diagram: 8017, 8018
Min Max Factory setting
- [°C] - [°C] - [°C]
r0633[0...n] Mot_temp_mod rotor temperature / Mod rotor temp
Access level: 4 Calculated: - Data type: FloatingPoint32
Can be changed: - Scaling: p2006 Dyn. index: MDS
Unit group: 21_1 Unit selection: p0505 Func. diagram: 8018
Min Max Factory setting
- [°C] - [°C] - [°C]