3 Function diagrams
3.9 Safety Integrated Basic Functions
SINAMICS G120 Control Units CU240B-2/CU240E-2
632 List Manual (LH11), 01/2016, A5E33839529
Fig. 3-63 2804 – Status words
- 2804 -
Function diagram
87654321
fp_2804_97_02.vsd
Safety Integrated Basic Functions
G120 CU240E-2
09.12.2015 V4.7.6
Status words
1
9
10
...
15
0[2810.4]
[2810.7]
[2802.5]
[2802.8]
1
0
31
[2810.5]
[2802.7]
... ...
SI status P1
r9772
r9772
Status word Safety Integrated
Processor 1
Bit No.
1 = STO selected on Processor 1
1 = STO active on Processor 1
Reserved
1 = STOP A cannot be acknowledged, active
1 = STOP A active
Reserved
1 = STOP F active
Bit No.
Reserved
Status word Safety Integrated
Processor 1 and Processor 2
1 = STO selected in drive
1 = STO active in drive
1 = The shutdown paths must be tested
17
18
16
19
20
1 = STO cause: Safety commissioning mode
1 = STO cause: selection via terminal (Basic
Functions)
1 = STO cause: selection via motion
monitoring functions
1 = STO cause: actual value missing
1 = STO cause: selection PROFIsafe (Basic
Functions)
SI status P1+P2
r9773
r9773
1
0 &
&
SI Status P2
r9872
r9872
Bit No.
Status word Safety Integrated Processor2
1 = STO selected on Processor 2
1 = STO active on Processor 2
Status (Processor 1 + Processor 2)Status (Processor 2)Status (Processor 1)
...
Reserved
9
1 = STOP A cannot be acknowledged, active
10
1 = STOP A active
...
Reserved
15
1 = STOP F active
16
1 = STO cause: Safety commissioning mode
17
1 = STO cause: selection via terminal (Basic
Functions)
18
1 = STO cause: selection via motion
monitoring functions
19
Reserved
20
1 = STO cause: selection PROFIsafe (Basic
Functions)
[2800.3]
[2810.2]
[2802.7]
[2802.8]
[2802.5]
[2800.3]
[2810.2]
[2810.4]
[2810.6]
[2810.2]
[2810.2]
[2810.2]
[2819.8]
[2810.2]
7
8
1 = STO terminal state on Processor 1 (Basic
Functions)
Reserved
7
8
1 = STO terminal state on Processor 2
Reserved
[2810.2] [2810.2]
21
1 = STO cause selection on processor 2
21
1 = STO cause selection on processor 1
25
1 = STO cause, selection via terminal on
Power Module
25[2812.6] [2812.6]
<1>
<1>
<1> Only for PM240-2 FS D-F.
30[2810.6]
1 = PM terminals shutdown paths must be
tested
<1>
1 = STO cause, selection via terminal on
Power Module
...
Reserved
...
Reserved