4 Faults and alarms
4.2 List of faults and alarms
F30683 SI Motion P2: SLS enable missing
Message class: Error in the parameterization / configuration / commissioning procedure (18)
Reaction: OFF2
Acknowledge: IMMEDIATELY (POWER ON)
Cause: The safety-relevant function "SLS" is not enabled in p9301 although other safety-relevant monitoring functions are
enabled.
Note:
This message does not result in a safety stop response.
Remedy: Enable the function "SLS" (p9301.0) and carry out a POWER ON.
Note:
Save the changes before POWER ON (copy from RAM to ROM).
SLS: Safely Limited Speed
See also: p9301 (SI Motion enable safety functions (processor 2))
F30692 SI Motion P2: Parameter value not permitted for encoderless
Message class: Error in the parameterization / configuration / commissioning procedure (18)
Reaction: OFF2
Acknowledge: IMMEDIATELY (POWER ON)
Cause: For encoderless motion monitoring functions, the parameter cannot be parameterized with this value.
Note:
This message does not result in a safety stop response.
Fault value (r0949, interpret decimal):
Parameter number with the incorrect value.
See also: p9301 (SI Motion enable safety functions (processor 2))
Remedy: Correct the parameter specified in the fault value.
See also: p9301 (SI Motion enable safety functions (processor 2)), p9501 (SI Motion enable safety functions
(processor 1))
A30693 (F) SI P2: Safety parameter settings changed, POWER ON required
Message class: Error in the parameterization / configuration / commissioning procedure (18)
Reaction: NONE
Acknowledge: NONE
Cause: Safety parameters have been changed; these will only take effect following a POWER ON.
Notice:
All changed parameters of the safety motion monitoring functions will only take effect following a POWER ON.
Alarm value (r2124, interpret decimal):
Parameter number of the safety parameter which has changed, necessitating a POWER ON.
Remedy: - execute the function "Copy RAM to ROM".
- carry out a POWER ON (switch-off/switch-on).
C30700 SI Motion P2: STOP A initiated
Message class: Safety monitoring channel has identified an error (10)
Reaction: OFF2
Acknowledge: IMMEDIATELY (POWER ON)
Cause: The drive is stopped via a STOP A (pulses are suppressed via the safety switch-off signal path of processor 1).
Possible causes:
- stop request from processor 1.
- Pulses not suppressed after test stop selection.
- subsequent response to the message C30706 "SI Motion P2: SAM/SBR limit exceeded".
- subsequent response to the message C30714 "SI Motion P2: Safely Limited Speed exceeded".
- subsequent response to the message C30701 "SI Motion P2: STOP B initiated".