SINAMICS G120 Control Units CU240B-2/CU240E-2
List Manual (LH11), 01/2016, A5E33839529
115
2 Parameters
2.2 List of parameters
Description: Activates the absolute value generation for the analog outputs.
Value: 0: No absolute value generation
1: Absolute value generation switched in
Index: [0] = AO0 (T 12/13)
[1] = AO1 (T 26/27)
Note: AO: Analog Output
T: Terminal
Description: Sets the analog output type.
p0776[x] = 1 corresponds to a voltage output (p0774, p0778, p0780 are displayed in V).
p0776[x] = 0, 2 corresponds to a current output (p0774, p0778, p0780 are displayed in mA).
Value: 0: Current output (0 mA ... +20 mA)
1: Voltage output (0 V ... +10 V)
2: Current output (+4 mA ... +20 mA)
Index: [0] = AO0 (T 12/13)
[1] = AO1 (T 26/27)
Note: When changing p0776, the parameters of the scaling characteristic (p0777, p0778, p0779, p0780) are overwritten
with the following default values:
For p0776 = 0, p0777 is set to 0.0 %, p0778 = 0.0 mA, p0779 = 100.0 % and p0780 to 20.0 mA.
For p0776 = 1, p0777 is set to 0.0 %, p0778 = 0.0 V, p0779 = 100.0 % and p0780 to 10.0 V.
For p0776 = 2, p0777 is set to 0.0 %, p0778 = 4.0 mA, p0779 = 100.0 % and p0780 to 20.0 mA.
Description: Sets the scaling characteristic for the analog outputs.
The scaling characteristic for the analog outputs is defined using 2 points.
This parameter specifies the x coordinate (percentage) of the 1st value pair of the characteristic.
Index: [0] = AO0 (T 12/13)
[1] = AO1 (T 26/27)
Dependency: Refer to: p0776
Notice: This parameter is automatically overwritten when changing p0776 (type of analog outputs).
Note: The parameters for the characteristic do not have a limiting effect.
p0775[0...1] CU analog outputs activate absolute value generation / CU AO absVal act
Access level: 2 Calculated: - Data type: Integer16
Can be changed: T Scaling: - Dyn. index: -
Unit group: - Unit selection: - Func. diagram: 9572
Min Max Factory setting
0 1 0
p0776[0...1] CU analog outputs type / CU AO type
Access level: 2 Calculated: - Data type: Integer16
Can be changed: U, T Scaling: - Dyn. index: -
Unit group: - Unit selection: - Func. diagram: 9572
Min Max Factory setting
0 2 0
p0777[0...1] CU analog outputs characteristic value x1 / CU AO char x1
Access level: 2 Calculated: - Data type: FloatingPoint32
Can be changed: U, T Scaling: - Dyn. index: -
Unit group: - Unit selection: - Func. diagram: 9572
Min Max Factory setting
-1000.00 [%] 1000.00 [%] 0.00 [%]