4 Faults and alarms
4.2 List of faults and alarms
F01681 SI Motion P1 (CU): Incorrect parameter value
Message class: Error in the parameterization / configuration / commissioning procedure (18)
Reaction: OFF2
Acknowledge: IMMEDIATELY (POWER ON)
Cause: The parameter cannot be parameterized with this value.
Note:
This fault does not result in a safety stop response.
Fault value (r0949, interpret decimal):
yyyyxxxx dec: yyyy = supplementary information, xxxx = parameter
yyyy = 0:
No information available.
xxxx = 9501:
It is not permissible to enable the function "n < nx hysteresis and filtering" (p9501.16) in conjunction with the function
"Extended functions without selection" (p9601.5).
xxxx = 9522:
The gear stage was set too high.
xxxx = 9547:
Parameter p9547 has been set too low.
xxxx = 9585:
For Safety without encoder and synchronous motor, p9585 must be set to 4.
Remedy: Correct the parameter value.
If xxxx = 9547:
With hysteresis/filtering enabled (p9501.16 = 1), the following applies:
Set parameters p9546/p9346 and p9547/p9347 acc. to the following rule: p9546 >= 2 x p9547; p9346 >= 2 x p9347
If xxxx = 9522 and 9585:
Correct the parameter value.
F01682 SI Motion P1 (CU): Monitoring function not supported
Message class: Error in the parameterization / configuration / commissioning procedure (18)
Reaction: OFF2
Acknowledge: IMMEDIATELY (POWER ON)
Cause: The monitoring function enabled in p9501, p9601 or p9801 is not supported in this firmware version.
Note:
This fault results in a STOP A that cannot be acknowledged.
Fault value (r0949, interpret decimal):
1: Monitoring function SLP not supported (p9501.1).
2: Monitoring function SCA not supported (p9501.7 and p9501.8 ... 15).
3: Monitoring function SLS override not supported (p9501.5).
4: Monitoring function external ESR activation not supported (p9501.4).
5: Monitoring function F-DI in PROFIsafe not supported (p9501.30).
6: Enable actual value synchronization not supported (p9501.3).
9: Monitoring function not supported by the firmware or enable bit not used.
11: Only encoderless monitoring functions integrated in the drive are supported.
12: Safety Integrated for SINUMERIK is not supported on this Control Unit.
20: Motion monitoring functions integrated in the drive are only supported in conjunction with PROFIsafe
(p9501/p9601.1 ... 2 and p9801.1 ... 2).
21: PROFIsafe only supported in conjunction with motion monitoring functions integrated in the drive (p9501/p9601.1
... 2 and p9801.1 ... 2).
23: CU240 does not support monitoring functions requiring an encoder.
25: Drive-integrated motion monitoring functions not supported (p9501, p9601.2).
28: Encoderless monitoring functions are not supported for synchronous motors (p9507.2).