2 Parameters
2.2 List of parameters
SINAMICS G120 Control Units CU240B-2/CU240E-2
158 List Manual (LH11), 01/2016, A5E33839529
Description: Sets the signal source for jog 2.
Recommendation: When the setting for this binector input is changed, the motor can only be switched on by means of an appropriate
signal change of the source.
Dependency: Refer to: p0840, p1059
Notice: The drive is enabled for jogging using BI: p1055 or BI: p1056.
The command "ON/OFF1" can be issued using BI: p0840 or using BI: p1055/p1056.
Only the signal source that was used to switch on can also be used to switch off again.
Description: Sets the speed for jog 1.
Jogging (JOG) is level-triggered, and allows the motor to be incrementally traversed.
Dependency: Refer to: p1055, p1056
Description: Sets the speed for jog 2.
Jogging (JOG) is level-triggered, and allows the motor to be incrementally traversed.
Dependency: Refer to: p1055, p1056
Description: Sets the speed limit effective in the setpoint channel.
Dependency: Refer to: p1082, p1083, p1085, p1086, p1088
p1056[0...n] BI: Jog bit 1 / Jog bit 1
CU240B-2
CU240E-2
CU240E-2_F
Access level: 3 Calculated: - Data type: U32 / Binary
Can be changed: T Scaling: - Dyn. index: CDS, p0170
Unit group: - Unit selection: - Func. diagram: 2501, 3030
Min Max Factory setting
- - 0
p1058[0...n] Jog 1 speed setpoint / Jog 1 n_set
Access level: 2 Calculated: - Data type: FloatingPoint32
Can be changed: T Scaling: - Dyn. index: DDS, p0180
Unit group: 3_1 Unit selection: p0505 Func. diagram: 3001, 3030
Min Max Factory setting
-210000.000 [rpm] 210000.000 [rpm] 150.000 [rpm]
p1059[0...n] Jog 2 speed setpoint / Jog 2 n_set
Access level: 2 Calculated: - Data type: FloatingPoint32
Can be changed: T Scaling: - Dyn. index: DDS, p0180
Unit group: 3_1 Unit selection: p0505 Func. diagram: 3001, 3030
Min Max Factory setting
-210000.000 [rpm] 210000.000 [rpm] -150.000 [rpm]
p1063[0...n] Setpoint channel speed limit / Setp_chan n_lim
Access level: 3 Calculated: - Data type: FloatingPoint32
Can be changed: U, T Scaling: - Dyn. index: DDS, p0180
Unit group: 3_1 Unit selection: p0505 Func. diagram: 3040
Min Max Factory setting
0.000 [rpm] 210000.000 [rpm] 210000.000 [rpm]