2 Parameters
2.2 List of parameters
For bit 05:
The threshold value is set in p1226 and the delay time in p1228.
For bit 06:
The hysteresis is set in p2162.
For bit 07:
The threshold value is set in p2163 and the hysteresis is set in p2164.
For bit 08:
The threshold value is set in p2170 and the delay time in p2171.
For bit 09, 10:
The threshold value is set in p2172 and the delay time in p2173.
For bit 11:
The threshold value is set in p2179 and the delay time in p2180.
For bit 12:
The threshold value is set in p2182, the hysteresis in p2162, and the delay time (for canceling the signal) in p2152.
For bit 13:
Only for internal Siemens use.
Description: Display and BICO output for the second status word of the monitoring functions.
Note: For bit 10:
The torque threshold value 1 is set in p2174.
For bit 12:
This bit is reset after the fault cause disappears, even if the fault itself is still present.
Description: Display and BICO output for the third status word of the monitoring functions.
r2198.0...13 CO/BO: Status word monitoring 2 / ZSW monitor 2
Access level: 3 Calculated: - Data type: Unsigned16
Can be changed: - Scaling: - Dyn. index: -
Unit group: - Unit selection: - Func. diagram: 2536
Min Max Factory setting
- - -
Bit field: Bit Signal name 1 signal 0 signal FP
00 |n_act| <= speed threshold value 5 Yes No 8023
01 |n_act| > speed threshold value 5 Yes No 8023
02 |n_act| <= speed threshold value 6 Yes No 8023
03 |n_act| > speed threshold value 6 Yes No 8023
04 |n_set| < p2161 Yes No 8011
05 n_set > 0 Yes No 8011
06 Motor blocked Yes No 8012
07 Motor stalled Yes No 8012
08 |I_act| < I_threshold value p2170 Yes No 8022
09 |M_act| > torque threshold value 1 and
n_set reached
Yes No 8023
10 |M_set| < torque threshold value 1 Yes No 8012
11 Load in the alarm range Yes No 8013
12 Load in the fault range Yes No 8013
13 |M_act| > torque threshold value 1 Yes No 8023
r2199.0...11 CO/BO: Status word monitoring 3 / ZSW monitor 3
Access level: 3 Calculated: - Data type: Unsigned16
Can be changed: - Scaling: - Dyn. index: -
Unit group: - Unit selection: - Func. diagram: 2537
Min Max Factory setting
- - -
Bit field: Bit Signal name 1 signal 0 signal FP
00 |n_act| < speed threshold value 3 Yes No 8010
01 f or n comparison value reached or
exceeded
Yes No 8010