2 Parameters
2.2 List of parameters
SINAMICS G120 Control Units CU240B-2/CU240E-2
32 List Manual (LH11), 01/2016, A5E33839529
Notice: This smoothed signal is not suitable for diagnostics or evaluation of dynamic operations. In this case, the
unsmoothed value should be used.
Note: Smoothing time constant = 300 ms
The signal is not suitable as a process quantity and may only be used as a display quantity.
The absolute current actual value is available smoothed (r0027) and unsmoothed (r0068).
Description: Displays the smoothed actual value of the modulation depth.
Dependency: Refer to: r0074
Note: Smoothing time constant = 100 ms
The signal is not suitable as a process quantity and may only be used as a display quantity.
The modulation depth is available smoothed (r0028) and unsmoothed (r0074).
Description: Displays the smoothed field-generating actual current.
Dependency: Refer to: r0076
Note: Smoothing time constant = 300 ms
The signal is not suitable as a process quantity and may only be used as a display quantity.
The field-generating current actual value is available smoothed (r0029) and unsmoothed (r0076).
Description: Displays the smoothed torque-generating actual current.
Dependency: Refer to: r0078
Note: Smoothing time constant = 300 ms
The signal is not suitable as a process quantity and may only be used as a display quantity.
The torque-generating current actual value is available smoothed (r0030) and unsmoothed (r0078).
Description: Displays the smoothed torque actual value.
Dependency: Refer to: r0080
Note: Smoothing time constant = 100 ms
The signal is not suitable as a process quantity and may only be used as a display quantity.
The torque actual value is available smoothed (r0031) and unsmoothed (r0080).
r0028 Modulation depth smoothed / Mod_depth smth
Access level: 4 Calculated: - Data type: FloatingPoint32
Can be changed: - Scaling: p2002 Dyn. index: -
Unit group: - Unit selection: - Func. diagram: 5730, 6799, 8950
Min Max Factory setting
- [%] - [%] - [%]
r0029 Current actual value field-generating smoothed / Id_act smooth
Access level: 4 Calculated: - Data type: FloatingPoint32
Can be changed: - Scaling: p2002 Dyn. index: -
Unit group: - Unit selection: - Func. diagram: 6799
Min Max Factory setting
- [Arms] - [Arms] - [Arms]
r0030 Current actual value torque-generating smoothed / Iq_act smooth
Access level: 4 Calculated: - Data type: FloatingPoint32
Can be changed: - Scaling: p2002 Dyn. index: -
Unit group: - Unit selection: - Func. diagram: 6799
Min Max Factory setting
- [Arms] - [Arms] - [Arms]
r0031 Actual torque smoothed / M_act smooth
Access level: 2 Calculated: - Data type: FloatingPoint32
Can be changed: - Scaling: p2003 Dyn. index: -
Unit group: 7_1 Unit selection: p0505 Func. diagram: 5730, 6799
Min Max Factory setting
- [Nm] - [Nm] - [Nm]