EasyManua.ls Logo

Siemens SINAMICS G120 - Fig. 3-27 2446 - PROFIdrive - STW3 control word interconnection

Siemens SINAMICS G120
924 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
3 Function diagrams
3.5 Communication PROFIdrive (PROFIBUS/PROFINET), EtherNet/IP
SINAMICS G120 Control Units CU240B-2/CU240E-2
592 List Manual (LH11), 01/2016, A5E33839529
Fig. 3-27 2446 – PROFIdrive - STW3 control word interconnection
- 2446 -
Function diagram
87654321
fp_2446_97_51.vsd
PROFIdrive (PROFIBUS/PROFINET), EtherNet/IP
CU240B/E-2_DP/PN
09.12.2015 V4.7.6
PROFIdrive - STW3 control word interconnection
STW3.0
STW3.1
STW3.2
STW3.3
STW3.4
STW3.5
STW3.6
STW3.8
STW3.9
STW3.11
STW3.12
STW3.13
STW3.14
STW3.15
STW3.7
STW3.10
p1022[0] = r2093.2
p1023[0] = r2093.3
p0820 = r2093.4
p0821 = r2093.5
-
-
p2200[0] = r2093.8
p1230[0] = r2093.9
-
p1492[0] = r2093.11
p1501[0] = r2093.12
p2106[0] = r2093.13
-
p0811[0] = r2093.15
p1020[0] = r2093.0
p1021[0] = r2093.1
[2513.2]
[2513.2]
[2513.2]
[2513.2]
-
-
[2513.2]
[2513.2]
-
[2513.2]
[2513.2]
[2513.2]
-
[2513.2]
[3010.2]
[2513.2]
[3010.2]
[3010.2]
[8565.2]
[8565.2]
-
-
[7958.4]
[7017.1]
-
[6030.1]
[6060.1]
[8060.1]
-
[8560.3]
[3010.2]
[3010.2]
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
Signal targets for STW3 in Interface Mode SINAMICS
Signal Meaning
Interconnection
parameters
[Function diagram]
internal control word
[Function diagram]
signal target
Inverted
Used in telegram 350.
1 = Fixed setp bit 0
1 = Fixed setp bit 1
1 = Fixed setp bit 2
1 = Fixed setp bit 3
1 = DDS select. bit 0
1 = DDS select. bit 1
Reserved
Reserved
1 = Technology controller enable
1 = DC braking active
Reserved
1 = Droop enable
1 = Torque control
0 = External fault 1 (F07860)
Reserved
1 = CDS bit 1
<1>
<1>

Table of Contents

Other manuals for Siemens SINAMICS G120

Related product manuals