2 Parameters
2.2 List of parameters
SINAMICS G120 Control Units CU240B-2/CU240E-2
48 List Manual (LH11), 01/2016, A5E33839529
Description: Display and connector output for actual torque value.
Index: [0] = Unsmoothed
[1] = Smoothed with p0045
Dependency: Not visible with application class: "Standard Drive Control" (SDC, p0096 = 1)
Refer to: r0031, p0045
Note: The value is available smoothed (r0031 with 100 ms, r0080[1] with p0045) and unsmoothed (r0080[0]).
Description: Displays the torque utilization as a percentage.
The torque utilization is obtained from the required smoothed torque referred to the torque limit.
Dependency: This parameter is only available for vector control. For U/f control r0081 = 0 %.
Not visible with application class: "Standard Drive Control" (SDC, p0096 = 1)
Refer to: r0033
Note: The torque utilization is available smoothed (r0033) and unsmoothed (r0081).
The torque utilization is obtained from the required torque referred to the torque limit as follows:
- Positive torque: r0081 = (r0079 / r1538) * 100 %
- Negative torque: r0081 = (-r0079 / -r1539) * 100 %
Description: Displays the instantaneous active power.
Index: [0] = Unsmoothed
[1] = Smoothed with p0045
[2] = Electric power
Dependency: Refer to: r0032
Note: The mechanical active power is available smoothed (r0032 with 100 ms, r0082[1] with p0045) and unsmoothed
(r0082[0]).
Description: Displays the flux setpoint.
Dependency: Not visible with application class: "Standard Drive Control" (SDC, p0096 = 1)
r0080[0...1] CO: Torque actual value / M_act
Access level: 3 Calculated: - Data type: FloatingPoint32
Can be changed: - Scaling: p2003 Dyn. index: -
Unit group: 7_1 Unit selection: p0505 Func. diagram: 6714, 6799
Min Max Factory setting
- [Nm] - [Nm] - [Nm]
r0081 CO: Torque utilization / M_Utilization
Access level: 4 Calculated: - Data type: FloatingPoint32
Can be changed: - Scaling: PERCENT Dyn. index: -
Unit group: - Unit selection: - Func. diagram: 8012
Min Max Factory setting
- [%] - [%] - [%]
r0082[0...2] CO: Active power actual value / P_act
Access level: 3 Calculated: - Data type: FloatingPoint32
Can be changed: - Scaling: r2004 Dyn. index: -
Unit group: 14_5 Unit selection: p0505 Func. diagram: 6714, 6799
Min Max Factory setting
- [kW] - [kW] - [kW]
r0083 CO: Flux setpoint / Flex setp
Access level: 4 Calculated: - Data type: FloatingPoint32
Can be changed: - Scaling: PERCENT Dyn. index: -
Unit group: - Unit selection: - Func. diagram: 5722
Min Max Factory setting
- [%] - [%] - [%]

Table of Contents