EasyManua.ls Logo

Siemens SINAMICS G120 - p2290[0...n] BI: Technology controller limiting enable; Tec_ctrl lim enab; p2291 CO: Technology controller maximum limiting; Tec_ctrl max_lim; p2292 CO: Technology controller minimum limiting; Tec_ctrl min_lim; p2293 Technology controller ramp-up;ramp-down time; Tec_ctr t_RU;RD

Siemens SINAMICS G120
924 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
2 Parameters
2.2 List of parameters
SINAMICS G120 Control Units CU240B-2/CU240E-2
336 List Manual (LH11), 01/2016, A5E33839529
Description: Sets the signal source to enable the technology controller output.
The technology controller output is enabled with a 1 signal.
The technology controller output is held with a 0 signal.
Description: Sets the maximum limit of the technology controller.
Dependency: Refer to: p2292
Caution: The maximum limit must always be greater than the minimum limit (p2291 > p2292).
Description: Sets the minimum limit of the technology controller.
Dependency: Refer to: p2291
Caution: The maximum limit must always be greater than the minimum limit (p2291 > p2292).
Description: Sets the ramping time for the output signal of the technology controller.
Dependency: Refer to: p2291, p2292
Note: The time refers to the set maximum and minimum limits (p2291, p2292).
Description: Display and connector output for the output signal of the technology controller.
Dependency: Refer to: p2295
p2290[0...n] BI: Technology controller limiting enable / Tec_ctrl lim enab
Access level: 2 Calculated: - Data type: U32 / Binary
Can be changed: T Scaling: - Dyn. index: CDS, p0170
Unit group: - Unit selection: - Func. diagram: 7958
Min Max Factory setting
- - 1
p2291 CO: Technology controller maximum limiting / Tec_ctrl max_lim
Access level: 3 Calculated: - Data type: FloatingPoint32
Can be changed: U, T Scaling: PERCENT Dyn. index: -
Unit group: - Unit selection: - Func. diagram: 7958
Min Max Factory setting
-200.00 [%] 200.00 [%] 100.00 [%]
p2292 CO: Technology controller minimum limiting / Tec_ctrl min_lim
Access level: 3 Calculated: - Data type: FloatingPoint32
Can be changed: U, T Scaling: PERCENT Dyn. index: -
Unit group: - Unit selection: - Func. diagram: 7958
Min Max Factory setting
-200.00 [%] 200.00 [%] 0.00 [%]
p2293 Technology controller ramp-up/ramp-down time / Tec_ctr t_RU/RD
Access level: 3 Calculated: - Data type: FloatingPoint32
Can be changed: U, T Scaling: - Dyn. index: -
Unit group: - Unit selection: - Func. diagram: 7958
Min Max Factory setting
0.00 [s] 100.00 [s] 1.00 [s]
r2294 CO: Technology controller output signal / Tec_ctrl outp_sig
Access level: 2 Calculated: - Data type: FloatingPoint32
Can be changed: - Scaling: PERCENT Dyn. index: -
Unit group: - Unit selection: - Func. diagram: 7958
Min Max Factory setting
- [%] - [%] - [%]

Table of Contents

Other manuals for Siemens SINAMICS G120

Related product manuals