SINAMICS G120 Control Units CU240B-2/CU240E-2
List Manual (LH11), 01/2016, A5E33839529
119
2 Parameters
2.2 List of parameters
Description: Sets the setpoint for the input signals in the digital input simulation mode.
Dependency: The simulation of a digital input is selected using p0795.
Refer to: p0795
Note: This parameter is not saved when data is backed up (p0971).
AI: Analog Input
DI: Digital Input
T: Terminal
Description: Sets the simulation mode for the analog inputs.
Value: 0: Terminal evaluation for analog input x
1: Simulation for analog input x
Index: [0] = AI0 (T. 3/4)
[1] = AI1 (T. 10/11)
Dependency: The setpoint for the input voltage is specified via p0798.
Refer to: p0798
Note: This parameter is not saved when data is backed up (p0971).
AI: Analog Input
Description: Sets the setpoint for the input value in the simulation mode of the analog inputs.
Index: [0] = AI0 (T. 3/4)
[1] = AI1 (T. 10/11)
Dependency: The simulation of an analog input is selected using p0797.
If AI x is parameterized as a voltage input (p0756), the setpoint is a voltage in V.
If AI x is parameterized as a current input (p0756), the setpoint is a current in mA.
Refer to: p0756, p0797
p0796 CU digital inputs simulation mode setpoint / CU DI simul setp
CU240E-2
CU240E-2_DP
CU240E-2 PN
CU240E-2_F
CU240E-2_PN_F
CU240E-2_DP_F
Access level: 3 Calculated: - Data type: Unsigned32
Can be changed: U, T Scaling: - Dyn. index: -
Unit group: - Unit selection: - Func. diagram: 2201, 2202, 2220,
2221, 2255, 2256
Min Max Factory setting
- - 0000 0000 0000 0000 bin
Bit field: Bit Signal name 1 signal 0 signal FP
00 DI 0 (T. 5) High Low -
01 DI 1 (T. 6) High Low -
02 DI 2 (T. 7) High Low -
03 DI 3 (T. 8) High Low -
04 DI 4 (T. 16) High Low -
05 DI 5 (T. 17) High Low -
11 DI 11 (T. 3, 4) AI 0 High Low -
12 DI 12 (T. 10, 11) AI 1 High Low -
p0797[0...1] CU analog inputs simulation mode / CU AI sim_mode
Access level: 3 Calculated: - Data type: Integer16
Can be changed: U, T Scaling: - Dyn. index: -
Unit group: - Unit selection: - Func. diagram: -
Min Max Factory setting
0 1 0
p0798[0...1] CU analog inputs simulation mode setpoint / CU AI sim setp
Access level: 3 Calculated: - Data type: FloatingPoint32
Can be changed: U, T Scaling: - Dyn. index: -
Unit group: - Unit selection: - Func. diagram: -
Min Max Factory setting
-50.000 2000.000 0.000