SINAMICS G120 Control Units CU240B-2/CU240E-2
List Manual (LH11), 01/2016, A5E33839529
117
2 Parameters
2.2 List of parameters
Description: Sets the signal source to invert the analog output signals.
Index: [0] = AO0 (T 12/13)
[1] = AO1 (T 26/27)
Note: AO: Analog Output
T: Terminal
Description: Displays the status of analog outputs.
Note: AO: Analog Output
Description: Setting and connector output to control the analog outputs via fieldbus.
Index: [0] = AO0 (T 12/13)
[1] = AO1 (T 26/27)
Dependency: Refer to: p0771
Note: AO: Analog Output
The following interconnections must be established to control the analog outputs via fieldbus:
- AO 0: p0771[0] with p0791[0]
- AO 1: p0771[1] with p0791[1]
Description: Sets the simulation mode for digital inputs.
p0782[0...1] BI: CU analog outputs invert signal source / CU AO inv S_src
Access level: 3 Calculated: - Data type: U32 / Binary
Can be changed: U, T Scaling: - Dyn. index: -
Unit group: - Unit selection: - Func. diagram: 9572
Min Max Factory setting
- - 0
r0785.0...1 BO: CU analog outputs status word / CU AO ZSW
Access level: 3 Calculated: - Data type: Unsigned16
Can be changed: - Scaling: - Dyn. index: -
Unit group: - Unit selection: - Func. diagram: 9572
Min Max Factory setting
- - -
Bit field: Bit Signal name 1 signal 0 signal FP
00 AO 0 negative Yes No -
01 AO 1 negative Yes No -
p0791[0...1] CO: Fieldbus analog outputs / Fieldbus AO
CU240B-2
CU240E-2
CU240E-2_F
Access level: 3 Calculated: - Data type: FloatingPoint32
Can be changed: U, T Scaling: PERCENT Dyn. index: -
Unit group: - Unit selection: - Func. diagram: -
Min Max Factory setting
-200.000 [%] 200.000 [%] 0.000 [%]
p0795 CU digital inputs simulation mode / CU DI simulation
CU240B-2
CU240B-2_DP
Access level: 3 Calculated: - Data type: Unsigned32
Can be changed: U, T Scaling: - Dyn. index: -
Unit group: - Unit selection: - Func. diagram: 2201, 2202, 2220,
2221, 2255, 2256
Min Max Factory setting
- - 0000 0000 0000 0000 bin
Bit field: Bit Signal name 1 signal 0 signal FP
00 DI 0 (T. 5) Simulation Terminal eval -
01 DI 1 (T. 6) Simulation Terminal eval -
02 DI 2 (T. 7) Simulation Terminal eval -
03 DI 3 (T. 8) Simulation Terminal eval -
11 DI 11 (T. 3, 4) AI 0 Simulation Terminal eval -