2 Parameters
2.2 List of parameters
SINAMICS G120 Control Units CU240B-2/CU240E-2
298 List Manual (LH11), 01/2016, A5E33839529
For value = 2 (OFF2):
Internal/external pulse inhibit.
For value = 3 (OFF3):
Braking along the OFF3 down ramp followed by a pulse inhibit.
For value = 5 (STOP2):
n_set = 0
For value = 6 (armature short-circuit, internal/DC braking):
This value can only be set for all drive data sets when p1231 = 4.
a) DC braking is not possible for synchronous motors.
b) DC braking is possible for induction motors.
Description: Sets the first signal source to acknowledge faults.
Notice: The parameter may be protected as a result of p0922 or p2079 and cannot be changed.
Note: A fault acknowledgment is triggered with a 0/1 signal.
Description: Sets the first signal source to acknowledge faults.
Notice: The parameter may be protected as a result of p0922 or p2079 and cannot be changed.
Note: A fault acknowledgment is triggered with a 0/1 signal.
Description: Sets the second signal source to acknowledge faults.
Note: A fault acknowledgment is triggered with a 0/1 signal.
p2103[0...n] BI: 1st acknowledge faults / 1st acknowledge
CU240B-2_DP
CU240E-2_DP
CU240E-2 PN
CU240E-2_PN_F
CU240E-2_DP_F
Access level: 3 Calculated: - Data type: U32 / Binary
Can be changed: U, T Scaling: - Dyn. index: CDS, p0170
Unit group: - Unit selection: - Func. diagram: 2441, 2442, 2443,
2447, 2475, 2546, 9220, 9677, 9678
Min Max Factory setting
- - [0] 2090.7
[1] 722.2
[2] 2090.7
[3] 2090.7
p2103[0...n] BI: 1st acknowledge faults / 1st acknowledge
CU240B-2
CU240E-2
CU240E-2_F
Access level: 3 Calculated: - Data type: U32 / Binary
Can be changed: U, T Scaling: - Dyn. index: CDS, p0170
Unit group: - Unit selection: - Func. diagram: 2441, 2442, 2443,
2447, 2475, 2546, 9220, 9677, 9678
Min Max Factory setting
- - [0] 722.2
[1] 0
[2] 0
[3] 0
p2104[0...n] BI: 2nd acknowledge faults / 2nd acknowledge
CU240B-2_DP
CU240E-2_DP
CU240E-2 PN
CU240E-2_PN_F
CU240E-2_DP_F
Access level: 3 Calculated: - Data type: U32 / Binary
Can be changed: U, T Scaling: - Dyn. index: CDS, p0170
Unit group: - Unit selection: - Func. diagram: 2546, 8060
Min Max Factory setting
- - [0] 722.2
[1] 0
[2] 0
[3] 0