2 Parameters
2.2 List of parameters
SINAMICS G120 Control Units CU240B-2/CU240E-2
274 List Manual (LH11), 01/2016, A5E33839529
Description: Sets the reference quantity for angle.
All angles specified as relative value are referred to this reference quantity.
The reference quantity corresponds to 100% or 4000 hex (word) or 4000 0000 hex (double word).
Dependency: This parameter is only updated during the automatic calculation (p0340 = 1, p3900 > 0) if motor commissioning was
carried out beforehand for drive data set zero. This means that the parameter is not locked against overwriting using
p0573 = 1.
Note: If a BICO interconnection is established between different physical quantities, then the particular reference quantities
are used as internal conversion factor.
Description: Sets the reference quantity for temperature.
All temperatures specified as relative value are referred to this reference quantity.
The reference quantity corresponds to 100% or 4000 hex (word) or 4000 0000 hex (double word).
Description: Sets the reference quantity for acceleration rates.
All acceleration rates specified as relative value are referred to this reference quantity.
The reference quantity corresponds to 100% or 4000 hex (word) or 4000 0000 hex (double word).
Dependency: This parameter is only updated during the automatic calculation (p0340 = 1, p3900 > 0) if motor commissioning was
carried out beforehand for drive data set zero. This means that the parameter is not locked against overwriting using
p0573 = 1.
Note: If a BICO interconnection is established between different physical quantities, then the particular reference quantities
are used as internal conversion factor.
The reference acceleration is calculated as follows:
p2007 = p2000 / 1 [s]
Description: Sets the baud rate for the commissioning interface (USS, RS232).
Value: 6: 9600 baud
7: 19200 baud
8: 38400 baud
9: 57600 baud
10: 76800 baud
p2005 Reference angle / Reference angle
Access level: 4 Calculated: p0340 = 1 Data type: FloatingPoint32
Can be changed: T Scaling: - Dyn. index: -
Unit group: - Unit selection: - Func. diagram: -
Min Max Factory setting
90.00 [°] 180.00 [°] 90.00 [°]
p2006 Reference temp / Ref temp
Access level: 3 Calculated: p0340 = 1 Data type: FloatingPoint32
Can be changed: T Scaling: - Dyn. index: -
Unit group: - Unit selection: - Func. diagram: -
Min Max Factory setting
50.00 [°C] 300.00 [°C] 100.00 [°C]
p2007 Reference acceleration / a_ref
Access level: 4 Calculated: p0340 = 1 Data type: FloatingPoint32
Can be changed: T Scaling: - Dyn. index: -
Unit group: - Unit selection: - Func. diagram: -
Min Max Factory setting
0.01 [rev/s²] 500000.00 [rev/s²] 0.01 [rev/s²]
p2010 Comm IF baud rate / Comm baud
Access level: 3 Calculated: - Data type: Integer16
Can be changed: T Scaling: - Dyn. index: -
Unit group: - Unit selection: - Func. diagram: -
Min Max Factory setting
6 12 12