Siemens SINAMICS G120 - p2295 CO: Technology controller output scaling; Tec_ctrl outp scal; p2296[0...n] CI: Technology controller output scaling; Tec_ctrl outp scal; p2297[0...n] CI: Technology controller maximum limit signal source; Tec_ctrMaxLimS_src; p2298[0...n] CI: Technology controller minimum limit signal source; Tec_ctrl min_l s_s

Siemens SINAMICS G120
924 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
SINAMICS G120 Control Units CU240B-2/CU240E-2
List Manual (LH11), 01/2016, A5E33839529
337
2 Parameters
2.2 List of parameters
Description: Sets the scaling for the output signal of the technology controller.
Description: Sets the signal source for the scaling value of the technology controller.
Dependency: Refer to: p2295
Description: Sets the signal source for the maximum limiting of the technology controller.
Dependency: Refer to: p2291
Note: In order that the output of the technology controller does not exceed the maximum speed limit, its upper limit p2297
should be connected to the actual maximum speed r1084.
In mode p2251 = 1, p2299 must also be connected to the output of the ramp-function generator r1150.
Description: Sets the signal source for the minimum limiting of the technology controller.
Dependency: Refer to: p2292
Note: If the technology controller is rotated in a negative direction in mode p2251 = 0, its lower limit p2298 should be
connected to the actual minimum speed r1087.
In mode p2251 = 1, p2299 must also be connected to the output of the ramp-function generator r1150.
Description: Sets the signal source for the offset of the output limiting of the technology controller.
Note: In mode p2251 = 1, p2299 must be connected to the output of ramp-function generator r1150 so that the technology
controller stops when the speed limits are reached (see also p2297, p2298).
p2295 CO: Technology controller output scaling / Tec_ctrl outp scal
Access level: 3 Calculated: - Data type: FloatingPoint32
Can be changed: U, T Scaling: PERCENT Dyn. index: -
Unit group: - Unit selection: - Func. diagram: 7958
Min Max Factory setting
-100.00 [%] 100.00 [%] 100.00 [%]
p2296[0...n] CI: Technology controller output scaling / Tec_ctrl outp scal
Access level: 3 Calculated: - Data type: U32 / FloatingPoint32
Can be changed: U, T Scaling: PERCENT Dyn. index: CDS, p0170
Unit group: - Unit selection: - Func. diagram: 7958
Min Max Factory setting
- - 2295[0]
p2297[0...n] CI: Technology controller maximum limit signal source / Tec_ctrMaxLimS_src
Access level: 3 Calculated: - Data type: U32 / FloatingPoint32
Can be changed: U, T Scaling: PERCENT Dyn. index: CDS, p0170
Unit group: - Unit selection: - Func. diagram: 7958
Min Max Factory setting
- - 1084[0]
p2298[0...n] CI: Technology controller minimum limit signal source / Tec_ctrl min_l s_s
Access level: 3 Calculated: - Data type: U32 / FloatingPoint32
Can be changed: U, T Scaling: PERCENT Dyn. index: CDS, p0170
Unit group: - Unit selection: - Func. diagram: 7958
Min Max Factory setting
- - 1087[0]
p2299[0...n] CI: Technology controller limit offset / Tech_ctrl lim offs
Access level: 3 Calculated: - Data type: U32 / FloatingPoint32
Can be changed: U, T Scaling: PERCENT Dyn. index: CDS, p0170
Unit group: - Unit selection: - Func. diagram: 7958
Min Max Factory setting
- - 0